SA8-01 220V AC 8 Wire

SA8-01 220V AC 8 Wire

Connection Diagram




This is a 8 wire connection for the motorised valve operated by 220V AC with feedback. 

Step by Step Guide

Details of the connections are as follows
1) Connect the Red Wire to the Phase of 220V AC
2) Connect the Black Wire to the Neutral of 220V AC
3) These 2 wires to be connected permanently, as this valve requires continuous power for both opening and closing of the valve
4) Green and Yellow wire to be shorted to open the valve
5) Green and Yellow wire if not shorted valve will be closed. 
6) No external power supply to be given to these 2 (Green and Yellow) wires.
7) Green and Yellow wires are carrying by self small DC signal to control the direction of the valve
8) The short can be maintained as long as the valve needs to be opened. But internally the motor will stop after full open. 
9) Blue wire to be connected to the Ground / Earth
10) Feedback input to be given the White Wire
11) Feedback output for the Valve open can be taken from Orange Wire
12) Feedback output for the Valve close can be taken from Brown Wire

FAQs

1) Q: Can I short the Green and Yellow Wire. and cut the power from Red and Black Wire. Will the valve close?
     A: No this connection is a stayput connection. That means the valve requires continuous power to both open and close the valve. 
2) Q: Do I need to connect a power supply to the Green Wire.
    A: Connecting any external supply to the Green and Yellow Wire will damage the electrical board. No external supply to given